'Fireflex R' Radiant Heat Reducing Fire Resisting Rolling Shutters

Integrity - 240 minutes

Application

 Standard Fire Shutter under test
Standard Fire
Shutter under test
 Fireflex Radiant Heat Reducing Shutter under test
Fireflex Radiant Heat Reducing Shutter under test

Tested by the Loss Prevention Council (Test Report 220737) to an integrity of 240 minutes (4 hours) for openings up to 50 m².

Fireflex is an obvious choice where increased risk of fire is a major concern. Fireflex provides a substantial safety barrier between the source of the fire and any precious or dangerously flammable stock. Fireflex is the perfect application for hospitals, shopping centres and industry.

Designed for internal or external applications where increased fire protection is required. It provides radiant heat protection with reliable operation through a simple control panel that can be adapted for a range of activation methods.

Fireflex is power operated with controlled descent following automatic activation. A safety brake is included as standard at the non motor end.

Due to its unique construction, the radiant heat levels around Fireflex drop from 65kw m² to 2.7 kw m². This means that combustible materials can be stored 500mm away from a 1200°C inferno, increasing floor space and reducing risk and break down of fire compartmentation.

Fireflex R also has a weighted sound reduction of 18 dB (BS5821 Part 3: 1984).

General Specification

 Fireflex Radiant Heat Reducing Shutter
Fireflex Radiant Heat Reducing Shutter

 

Curtain
Manufactured from pre galvanised material designed to provide a hollow section panel with ceramic infill. Each section is 100mm high with twin ribbed face for rigidity.

The curtain is held in position with purposely designed end fittings which act as a curtain alignment system. The bottom panel is terminated with a galvanised steel plate with horizontal and vertical slots.

Hood (Coil Casing)
All Fireflex R shutters include a galvanised sheet hood as standard with optional motor cover. (Motor cover always included if less than 2500mm high).

Guides
Formed from pre galvanised steel.

Endplates
Mild steel of appropriate thickness relative to door size.

Finish
Standard finish to all parts is galvanised.
Powder coated finish to a standard range of BS/RAL colours available at extra cost

Operation

Fireflex Shutters are power operated by a 3 phase & neutral motor with various options of release:

Level 1 Fusible Link Operation
Normal operation by push button station or keyswitch with fuse link to close shutter at local heat source of 75°C.

*Level 2 Alarm activation with manual reset
Normal operation by push button station or keyswitch with solenoid release to close shutter following fire alarm signal with manual reset of solenoid by pull cables.

*Level 3 Alarm activation with automatic reset
Normal operation by push button station or keyswitch with solenoid release to close shutter following fire alarm signal with automatic reset of solenoid once alarm is switched off by fully opening shutter.

*Level 4 Alarm activation with automatic reset and part close facility
Normal operation by push button station or keyswitch with solenoid release to close shutter following fire alarm signal with automatic reset of solenoid once alarm is switched off by fully opening shutter.

Shutter can also part close to act as a smoke curtain, fully closing after an adjustable delay. Shutter must have maintained supply for this function.

*For Level 2, 3 and 4 Audible Visual (with adjustable delay timer) can be included to one or both sides of the opening.

 Level One - Fire  Level Two - Fire

 Level Three - Fire

 Level Four - Fire

Fire Alarm requirements

The Fire Alarm circuit must provide the supply for the 24v DC solenoid (0.5 amps) with an initial supply of 3.5 amps for 20-30 m/seconds to release the shutter but only when in the alarm condition.

If the fire alarm is unable to provide a 24v DC supply a battery back up system is available at extra cost.

The 24v DC supply needs to be provided separately from that of the fire alarm system as under the requirements of BS5839 Clause 19, the connection of such equipment is specifically prohibited.

Syston Doors DO NOT include for connecting into the fire alarm circuit.

Note! To comply with current legislation fire shutters cannot be linked to fire alarm systems if they are over fire exits or are on a fire exit route. They can only be fitted with a device, which will close the shutter, by a local heat source i.e. fusible link.

 Fireflex - Radiation profile

Radiation profile showing the safe distance for storage of combustible materials from a 7m x 7m single, double and Radiant Heat Reducing shutter

 Fireflex - Irradiance

When comparing the performance of a conventional single skinned fire shutter with the FIREFLEX Radiant Heat Reducing Fire Shutter the above graph shows the reduction in radiated heat protection giving up to an increased performance protection of 96%


Return to Fire Rated Products intro page

 Click for Technical Information Sheet   Technical Information
for Fireflex R

(PDF - 417 KB)
   Fire Resisting Rolling Shutters & Doors Brochure   Fire Resisting Rolling Shutters & Doors Brochure

(PDF - 1.38 MB)
 Click for Colour Charts  

Colour Charts


 Top of page